  • Abstract
    For evaluating the lightning performance of power transmission lines by computer simulation, accurate modelling of tower footing is very important. In particular, the decrease of the earth resistance observed for high values of the current flowing from the tower to earth has to be considered. In this paper, different modelling approaches allowing the nonlinear behaviour of the tower footing to be taken into account are overviewed, and a new model to describe the soil ionization process is presented. The proposed model corresponds to considering the ionized soil region as an equifield shell. In order to represent the ionization phenomena, the values of the resistivity on the ionized region are decreased according to the local current density, and the electric field is kept at a critical value. Deionization of the soil is also taken into account. Simulation results are presented, and compared to the published results of experimental tests
  • Keywords
    earthing; lightning protection; poles and towers; power overhead lines; power system analysis computing; power transmission lines; accurate modelling; computer simulation; current density; current flow; earth resistance; electric field; equifield shell; lightning performance; power transmission lines; rod driven tower footing; soil ionization process; Computer simulation; Conductivity; Current density; Earth; Grounding; Ionization; Lightning; Poles and towers; Power transmission lines; Soil;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.517523
  • Filename
    517523