• DocumentCode
    1152463
  • Title

    Study on an Audible Noise Reduction Measure for the Filter Capacitors in the HVDC Converter Station Based on the MPP Absorber

  • Author

    Peng, Wu ; Shengchang, Ji ; Tao, Cao ; Yanming, Li ; Xiaolin, Li ; Yan, Li

  • Author_Institution
    State Key Lab. of Electr. Insulation & Power Equip., Xi´´an Jiaotong Univ., Xi´´an, China
  • Volume
    24
  • Issue
    4
  • fYear
    2009
  • Firstpage
    1756
  • Lastpage
    1762
  • Abstract
    Audible noise of the filter capacitors in the HVDC converter station is severe and as loud as the converter transformer and, therefore, needs to be reduced. A microperforated-panel (MPP) absorber can be used because of its fibre-free nature and attractive appearance. In this paper, based on the mechanism of sound generation of capacitors and the electroacoustical equivalent circuit model of the MPP absorber, the MPP absorber for noise reduction of the filter capacitor in the HVDC converter station is first proposed, and then it is designed and installed at the bottom of the capacitor. An audible noise experiment of the capacitor with the MPP absorber is performed and compared with a regular capacitor´s. The results validate that the MPP absorber is effective to reduce audible noise of the filter capacitors.
  • Keywords
    HVDC power convertors; power capacitors; substations; HVDC converter station; MPP absorber; audible noise reduction measure; electroacoustical equivalent circuit model; filter capacitors; microperforated-panel absorber; Audible noise reduction; HVDC converter station; filter capacitor; microperforated panel (MPP);
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2009.2021027
  • Filename