• DocumentCode
    1153559
  • Title

    A New Method for Part-Winding Starting of Polyphase Motors [includes discussion]

  • Author

    Alger, P.L. ; Agacinsky, Lorraine M.

  • Author_Institution
    FELLOW AIEE, General Electric Company, Schenectady, N. Y.
  • Volume
    74
  • Issue
    3
  • fYear
    1955
  • Abstract
    Part-winding or "step-starting" of polyphase induction motors for holding down the initial starting current inrush is on the increase. The conventional scheme provides two half-current starting contactors, each with three poles. The motors have dual-voltage 9-lead windings, arranged in two independent Y\´s, separately connected to the two contactors. The two contactors are closed in sequence with a few seconds\´ delay between, giving about 60 per cent (%) current on the first step. The delay must be very short, because the accelerating torque on half-winding is usually low, the motor may be noisy, and the rate of heating is high.
  • Keywords
    Acceleration; Contactors; DH-HEMTs; Delay; Differential equations; Equivalent circuits; Niobium; Steady-state; Voltage; Writing;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
  • Publisher
    ieee
  • ISSN
    0097-2460
  • Type

    jour

  • DOI
    10.1109/AIEEPAS.1955.4499251
  • Filename