• DocumentCode
    1154131
  • Title

    Co-ordination of Dry-Type Transformer Models with Transformer Geometry [includes discussion]

  • Author

    Whitman, L.C.

  • Author_Institution
    MEMBER AIEE, General Electric Company, Pittsfield, Mass.
  • Volume
    75
  • Issue
    3
  • fYear
    1956
  • Abstract
    The present practice of using different temperature classes of insulation in a single unit as indicated feasible by functional test codes1 and evaluation of component insulations2 make the knowledge of temperature gradients throughout the dry-type transformer of prime importance. A number of thermal effects of presently used dry-type transformer geometries are evaluated and data presented showing their interrelation. Some representative ratios of hot-spot temperature rises are given allowing a closer co-ordination between a dry-type transformer aging model and its prototype. Since winding height is a major factor, some corrections factoring this item with the general ratios are proposed.
  • Keywords
    Aging; Coils; Ducts; Geometry; Insulation testing; Power transformer insulation; Prototypes; Solid modeling; Temperature; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
  • Publisher
    ieee
  • ISSN
    0097-2460
  • Type

    jour

  • DOI
    10.1109/AIEEPAS.1956.4499309
  • Filename
    4499309