DocumentCode
1154765
Title
Influence of air gaps in stacked transformer cores consisting of several packages
Author
Loffler, Frank ; Pfutzner, Helmut ; Booth, Thomas ; Bengtsson, Claes ; Gramm, Kurt
Author_Institution
Inst. of Fundamentals & Theory of Electrotech., Univ. of Technol., Austria
Volume
30
Issue
2
fYear
1994
fDate
3/1/1994 12:00:00 AM
Firstpage
913
Lastpage
915
Abstract
The influence of air gap length g on core loss P and excitation S was investigated in model cores including linearized overlap regions. Special emphasis was put on the interaction of core packages with shifted air gap regions. There, normal flux components ΦZ arise into neighbouring, gapless package regions. The resulting planar eddy current losses proved to be proportional to the square of ΦZ. A correlation was established between local distributions of g, ΦZ, P and S
Keywords
eddy current losses; spark gaps; transformer cores; air gap length; air gaps; linearized overlap regions; planar eddy current losses; stacked transformer cores; Air gaps; Assembly; Bioelectric phenomena; Coils; Core loss; Eddy currents; Magnetic cores; Magnetic flux; Packaging; Transformer cores;
fLanguage
English
Journal_Title
Magnetics, IEEE Transactions on
Publisher
ieee
ISSN
0018-9464
Type
jour
DOI
10.1109/20.312443
Filename