    Short-Circuit Tests with Rapid Reclosing on the 220-Kv Mettlen-Lavorgo Line [includes discussion]

  • Author

    Schaer, F. ; Baltensperger, P.

  • Author_Institution
    MEMBER AIEE, Aare-Tessin Electricity Company, Ltd., Olten, Switzerland
  • Volume
    75
  • Issue
    3
  • fYear
    1956
  • Abstract
    Before the 220-kv Mettlen-Lavorgo line was finally put in service, the protection devices and the circuit breakers of the 100-kilometer (km)-long 220-kv transmission system with grounded neutral point were tested for rapid reclosing with short-circuit arcs. The tests described here demonstrate the trouble-free performance of high-speed distance relays, air-blast circuit breakers, and the accompanying reclosing equipment. In the case of the single-pole ground faults, the residual arc was extinguished after, at the most, two periods. No restrikes occurred with a dead time of more than 0.22 second for the 3-pole and 0.45 second for the single-pole interruptions, and the power supply could be continued.
  • Keywords
    Circuit breakers; Circuit testing; Costs; Equations; Fuel economy; Power generation economics; Production; System testing; Thermodynamics; Time measurement;