• DocumentCode
    1157881
  • Title

    Loading of Ventilated Dry-Type Transformers

  • Author

    Whitman, L.C.

  • Volume
    76
  • Issue
    3
  • fYear
    1957
  • fDate
    4/1/1957 12:00:00 AM
  • Firstpage
    1077
  • Lastpage
    1084
  • Abstract
    This is a continuation of the previously published data on the loading of sealed dry-type transformers.1 With the same representative core and coils as were used in the previous work, and the sealed tank replaced with a louvered casing, the winding temperature rises are measured for a variety of loads following several steady-state conditions. These data are converted to hottest-spot temperatures utilizing previously published hottest-spot increments and the allowable limits specified in the standards. Aging rates are those for the presently used materials in ventilated dry-type transformers. Insulation aging is computed for various overload cycles and the allowable loads determined for normal life expectancy as well as a few specified per cent loss-of-life criteria.
  • Keywords
    Aging; Brushes; Commutation; Frequency; Induction motor drives; Power transformer insulation; Temperature dependence; Temperature measurement; Thermal loading; Thermal resistance;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
  • Publisher
    ieee
  • ISSN
    0097-2460
  • Type

    jour

  • DOI
    10.1109/AIEEPAS.1957.4499721
  • Filename
    4499721