• DocumentCode
    1158636
  • Title

    Ampacity Test of a Silicone Foam Firestop in a Cable Tray

  • Author

    Herter, V.J. ; Barry, R.E. ; Began, T.A.

  • Author_Institution
    The Detroit Edison Company
  • Issue
    11
  • fYear
    1981
  • Firstpage
    4680
  • Lastpage
    4685
  • Abstract
    An ampacity (current loading) test was conducted on 600 volt cables in open top cable trays in a controlled atmosphere. The cable trays were placed in a simulated nuclear plant wall penetration with a silicone foam firestop. The purpose of the test was to determine whether the penetration and firestop would cause the conductor temperatures to exceed the temperature ratings of the insulation of the cables used at Fermi 2. Test results showed that the temperatures attained were not excessive, and that the IPCEA* Tables from which the conductors were selected may be conservative.
  • Keywords
    Cable insulation; Cable shielding; Conducting materials; Conductors; Copper; Fires; Insulation testing; Power cables; Power generation; Temperature;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1981.316811
  • Filename
    4110560