• DocumentCode
    1158857
  • Title

    Real Time Results with On-Line Network Equivalents for Control Center Applications

  • Author

    Housos, Efthymios ; Irisarri, Guillermo

  • Author_Institution
    AMERICAN ELECTRIC POWER SERVICE CORPORATION
  • Issue
    12
  • fYear
    1981
  • Firstpage
    4830
  • Lastpage
    4837
  • Abstract
    Extensive analysis and testing with real time data of the AEP system for various types of equivalencing techniques has been performed. It was found that for real time on-line applications the REI-type equivalents performed better than other equivalencing methods (Ward-type equivalents). It is shown that the equivalent updating procedure used for REI-type equivalents cannot be used for Ward-type equivalents. Ward-type equivalents which performed well for off-line planning applications and for some simulated real time applications did not work as well under realistic on-line conditions.
  • Keywords
    Performance analysis; Performance evaluation; Power system interconnection; Power system planning; Power system reliability; Power system simulation; Real time systems; Robustness; State estimation; System testing;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1981.316445
  • Filename
    4110588