DocumentCode
1159296
Title
Development for Measurement of Operating Parameters of Synchronous Generator and Control Systems
Author
Namba, M. ; Hosoda, J. ; Doi, S. ; Udo, M.
Author_Institution
Kansai Electric Power Co., Inc.
Issue
2
fYear
1981
Firstpage
618
Lastpage
628
Abstract
On load tests to measure operating parameters of apparatus in typical thermal and hydraulic power stations were performed. The results obtained by static characteristic tests of generator were greatly affected by magnetic saturation. Authors propose a new method to estimate on load synchronous reactances from no load factory tests. For dynamic characteristic test, authors conducted´a new arbitrary-axis load rejection method in addition to d-axis and q-axis load rejection method proposed by F. P. de Mello[1].
Keywords
Character generation; Control systems; Performance evaluation; Power generation; Power measurement; Production facilities; Saturation magnetization; Synchronous generators; Testing; Thermal loading;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1981.316918
Filename
4110643
Link To Document