• DocumentCode
    1159679
  • Title

    On The Origin, significance, and Minimization of Nonuniform Contamination Along HVDC Insulator Strings

  • Author

    Olsen, R.G. ; Daffe, J. ; Sarkinen, C.F.

  • Author_Institution
    Department of Electrical Engineering Washington State University
  • Issue
    3
  • fYear
    1981
  • fDate
    3/1/1981 12:00:00 AM
  • Firstpage
    971
  • Lastpage
    980
  • Abstract
    it is shown theoretically and experimentally that the electric force on charged airborne contaminants can cause the distribution of contaminant along the length of an insulator string energized by HVDC to be nonuniform. This nonuniformity causes a nonlinear voltage distribution along the string. As a result, some sections of the insulator string may be subject to electrical stresses high enough to initiate insulator failure. Comparative flashover tests between insulators with uniform and nonuniform contamination distributions confirm this hypothesis (i.e. that nonuniform contamination along the insulator string degrades HVDC insulator performance). It is also shown that grading rings can be attached to each end of an insulator string without creating air gaps less than those needed to protect against transient overvoltages. The grading rings modify the electric field in the vicinity of the string and cause the distribution of contamination along the string to be more uniform. This in turn may lead to improved insulator performance
  • Keywords
    Air gaps; Contamination; Degradation; Dielectrics and electrical insulation; Flashover; HVDC transmission; Insulator testing; Protection; Stress; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1981.316632
  • Filename
    4110689