Title :
Current Transformer Accuracy with Asymmetric and High Frequency Fault Currents
Author_Institution :
Power Technologies, Inc.
fDate :
3/1/1981 12:00:00 AM
Abstract :
The accuracy of two commercially available window current transformers is determined for asymmetrical 60 Hz fault currents and for lower magnitude higher frequency currents. The 4000: 5, window type CT´s tested are found to be accurate to within 3 percent for frequencies up to 25 kHz for burdens of less than 10 ohms. With an antiremanence gap, such a Ct can transform a fully offset fault current of 5000 amperes and 50 millisecond time constant with less than 3 percent error for a burden resistor of 0.5 ohms
Keywords :
Capacitance; Chromium; Circuit faults; Current transformers; Equivalent circuits; Fault currents; Frequency; Impedance; Testing; Transformer cores;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1981.316636