• DocumentCode
    1160233
  • Title

    Synchronous Machine Models by Standstill Frequency Response Tests

  • Author

    Coultes, M.E. ; Watson, Wilfred

  • Author_Institution
    Ontario Hydro Research Division
  • Issue
    4
  • fYear
    1981
  • fDate
    4/1/1981 12:00:00 AM
  • Firstpage
    1480
  • Lastpage
    1489
  • Abstract
    An approach to determining synchronous machine parameters by low-voltage frequency response tests with the machine stationary will be described. The tests are simple and safe. In addition, they provide a more detailed and complete model of the machine than the accepted standard methods/1/. The standard tests rely heavily on the measurement of large transients. As such, they are susceptible to any changes in saturation during the course of the measured transient. Furthermore, the accuracy and resolution with which a single transient can be measured are frequently insufficient to provide the detail required to model the solid iron rotor of a turbogenerator. The test method described herein avoids both of these problems as well as providing complete q-axis data which is not done by the standard tests.
  • Keywords
    Circuit testing; Equations; Equivalent circuits; Frequency measurement; Frequency response; Low voltage; Senior members; Stator windings; Synchronous machines; Transfer functions;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1981.316568
  • Filename
    4110757