Title :
Suppression of Temporary Overvoltages Caused by Transformer and AC Filter Inrush Currents at the Shin-Shinano Frequency Converter Station
Author :
Sakurai, T. ; Murotani, K. ; Oonishi, K.
Author_Institution :
Tokyo Electric Power Co., Inc.
fDate :
4/1/1981 12:00:00 AM
Abstract :
The temporary overvoltage problem associated with ac-dc converter stations is caused by the converter transfornmer Mnagnetizing inrush currents. A damping resistor type suppressor is introduced into the AC filter of the Shin-Shinano Frequency Converter Station to supprets such overvoltages. A bonsiderable suppression effect is noted during the field testing, and the validity of the overvoltage prediction by calculation is also confirmed by the measurements.
Keywords :
Analog-digital conversion; Capacitors; Damping; Filter bank; Frequency conversion; Harmonic filters; Power generation; Resistors; Surges; Testing;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1981.316549