DocumentCode
1160584
Title
Current Transformer Accuracy on Pulse-Burst-Modulated Circuits
Author
Emanuel, A.E. ; Gulachenski, E.M. ; Levitsky, F.J.
Author_Institution
Worcester Polytechnic Institute
Issue
4
fYear
1981
fDate
4/1/1981 12:00:00 AM
Firstpage
1766
Lastpage
1770
Abstract
The performance of metering-type current transformers connected in circuits with Pulse-Burst Modulation was studied. Measurements for Integral-Cycle and Half-Cycle Control are presented. Test results show that, when Integral-Cycle Control is used to regulate loads with power factors less than 0.95 lag, the recurrent transient component of the current could cause unacceptable increases in the current transformer phase-angle error. This paper considers four distinctive operation modes of Integral-Half- Cycle Control. It is shown that for only one of these modes the phase-angle error can be kept within acceptable limits. For this case the thyristor is turned on during an odd number of half- cycles and is off during an even number of half-cycles. A simple mathematical model explains the experimental results.
Keywords
Current transformers; Magnetic cores; Pulse circuits; Pulse modulation; Pulse power systems; Pulse transformers; Reactive power; Space heating; Thyristors; Welding;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1981.316515
Filename
4110795
Link To Document