DocumentCode :
1162521
Title :
Effect of Time Shift Between the two Voltage Components on Phase-to-Phase Insulation Strength
Author :
Kosztaluk, Romuald ; Lanoie, Robert ; Malewski, Ryszard ; Menemenlis, Christos ; Nguyen, Duc-Hai
Author_Institution :
Institut Energetyki
Issue :
7
fYear :
1981
fDate :
7/1/1981 12:00:00 AM
Firstpage :
3379
Lastpage :
3386
Abstract :
A study on the phase-to-phase strength of a conductor-conductor configuration was performed in IREQ´s High-Voltage Laboratory in an attempt to determine the influence of a time shift, ATcr, between the positive and negative voltage components on the 50% breakdown voltage. The gap tested was formed by two parallel conductors 6.7 m apart. Positive impulses of up to 2.3 MV, negative impulses of up to 3.2 MV and time shifts of up to 7.5 ms were used. The breakdown voltage, space charge and electric field on the electrode surface were monitored during the tests and photographs were taken with an image-converter camera.
Keywords :
Conductors; Costs; Dielectrics and electrical insulation; Laboratories; Reliability; Substations; Surges; Testing; Time measurement; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1981.316680
Filename :
4111017
Link To Document :
بازگشت