DocumentCode :
1162922
Title :
Analysis of Conductor Galloping Field Observations - Single Conductors
Author :
Rawlins, C.B.
Author_Institution :
Alcoa Conductor Products Company
Issue :
8
fYear :
1981
Firstpage :
3744
Lastpage :
3753
Abstract :
Phase-to-phase clearances often are increased in the design of overhead lines to minimize flashovers caused by galloping of ice-coated conductors in regions where that occurs. A collection of reports of the observed galloping behavior of operating lines has been analyzed with the objective of formulating improved guides for selection of increased clearances. Results of the analysis show the effects on galloping amplitudes of such line design parameters as span length and tension.
Keywords :
Assembly; Conductors; Economic forecasting; Flashover; Hardware; Power & Energy Society; Power generation economics; Printing; Senior members; Wires;
fLanguage :
English