DocumentCode :
1164354
Title :
Contributions to lightning research for transmission line compaction
Author :
de la Rosa, R. ; Ochoa, Manuel ; Bonilla, José L. ; Enríquez, Gilberto
Author_Institution :
Istituto de Investigaciones Electricas, Morelos, Mexico
Volume :
3
Issue :
2
fYear :
1988
fDate :
4/1/1988 12:00:00 AM
Firstpage :
716
Lastpage :
723
Abstract :
Research on lightning performance of compact transmission lines is presented. Various parameters affecting the tripout rate are described, particularly when reduced dielectric clearances are considered. By means of a series of laboratory impulse tests on a geometric scale guyed type structure, the critical flashover voltage of a compact inverted delta configuration is obtained. This parameter is used as an input of a digital program which estimates the lightning tripout rate expected for this type of tower. The compact design of a 400 kV transmission line is proposed and the requirements for future research work are anticipated
Keywords :
flashover; lightning; poles and towers; power transmission lines; 400 kV; compact inverted delta configuration; critical flashover voltage; geometric scale guyed type structure; lightning performance; lightning tripout rate; transmission line compaction; Compaction; Costs; Dielectrics; IEEE members; Lightning; Power transmission lines; Testing; Transmission line theory; Transmission lines; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.4310
Filename :
4310
Link To Document :
بازگشت