DocumentCode
1164430
Title
The Calculation of Overpressure in Metal-Enclosed Switchgear Due to Internal Arcing
Author
Lutz, F. ; Pietsch, G.
Author_Institution
Aachen Technical University
Issue
11
fYear
1982
Firstpage
4230
Lastpage
4236
Abstract
The mechanical stress of metal-enclosed switchgear installations due to fault arcs can be predicted by means of pressure calculation. In this paper a number of calculation methods is discussed. The results of pressure calculation are compared with pressure measurements performed in model switchgear cubicles. It is shown, that simplifying assumptions in some calculation methods lead to inaccurate results. Pressure calculation for switchgear cubicles with effective pressure relief openings should take into account the spatial limitation of arc energy input.
Keywords
Arc discharges; Electrodes; Gases; IEC standards; Insulation; Performance evaluation; Pressure measurement; Stress; Switchgear; Testing;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1982.317368
Filename