DocumentCode
1164502
Title
AC Fog Withstand Test on Contaminated Insulators by Steam Fog
Author
Arai, Noboru
Author_Institution
Central Research Institute of Electric Power Industry
Issue
11
fYear
1982
Firstpage
4316
Lastpage
4323
Abstract
This paper describes the results of an investigation into how steam fog parameters affect the withstand voltage of artificially contaminated insualtors by the fog withstand method. We established the correlation between the steam flow rate and liquid water content of the fog. The fog withstand voltage showed a lower value with little dispersion at about 3 to 10 g/m3 of the maximum liquid water content. The minimum fog withstand voltage agreed well with the minimum flashover voltage obtained under natural conditions. We suggest that, for the fog withstand test using steam fog, the ideal fog condition would be about 3 to 7 g/m3 of the maximum liquid water content of the fog.
Keywords
Boilers; Contamination; Flashover; Fluid flow; Insulator testing; Power transformer insulation; Surface resistance; Temperature; Voltage; Water pollution;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1982.317394
Filename
4111255
Link To Document