Title : 
Ligntning Insulation Coordination for a ±600 kV DC Gas Insulated Cable
         
        
            Author : 
Hileman, A.R. ; Flugum, R.W. ; Garrity, T.F.
         
        
            Author_Institution : 
Westinghouse Electric Corp.
         
        
        
        
        
        
            Abstract : 
To determine the required BIL of a +600 kV dc gas-insulated cable, a probabilistic insulation coordination study was performed. An equation was developed to determine the maximum voltage on the cable as a function of directly connected highly nonlinear surge protective devices (MO). After estimating the distribution of surge voltage magnitudes and shapes which arrive at the line-cable junction, the probability of flashover within the cable was determined. The results, analyzed in terms of mean time between failures, MTBF, verified that a 1300 kV BIL was adequate.
         
        
            Keywords : 
Cable insulation; Gas insulation; Nonlinear equations; Power cable insulation; Power cables; Shape; Surge Protective Devices - c62; Surge protection; Surges; Voltage;
         
        
        
            Journal_Title : 
Power Apparatus and Systems, IEEE Transactions on
         
        
        
        
        
            DOI : 
10.1109/TPAS.1982.317406