• DocumentCode
    1164787
  • Title

    Failure of Electromagnetic Voltage Transformer Due to Sustained Over-Voltage on Switch off - Preventive Measures

  • Author

    Igarwal, R.P. ; Saxena, N.S. ; Gupta, J.C. ; Sharma, B.S.

  • Author_Institution
    Indian Institute of Technology
  • Issue
    12
  • fYear
    1982
  • Firstpage
    4536
  • Lastpage
    4541
  • Abstract
    The damage to a 220 KV electromagnetic voltage transformer (EMVT) due to sustained over-voltage on switch-off by a circuit breaker (CB) fitted with grading capacitors, and subsequent studies for the steady-state period have already been reported [1]. In this paper, the pre-steady state period is analyzed and excellent agreement shown between field and analytical results. The concerned parameters for various makes of CB´s, EMVT´s and bus-bar capacitance have been collected and a. number of studies conducted. It is concluded that the control of. the EMVT saturation characteristic is superior compared to the measures su, ggested earlier to prevent such over-voltages. A suitable saturation characteristic for the worst case has been identified.
  • Keywords
    Capacitance; Circuit breakers; Electromagnetic analysis; Electromagnetic measurements; Power transformer insulation; Samarium; Steady-state; Substations; Switches; Voltage transformers;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1982.317306
  • Filename
    4111288