DocumentCode
1165521
Title
Effect of Solar Induced Current on Autotransformer Tertiary Windings
Author
Aspnes, J.D. ; Akasofu, S.-I.
Author_Institution
Electrical Engineering Dept. University of Alaska
Issue
3
fYear
1982
fDate
3/1/1982 12:00:00 AM
Firstpage
635
Lastpage
638
Abstract
Experimental results are presented showing the effect of solar induced current (SIC) in the series and common windings of an autotransformer on tertiary winding current. The three-phase autotransformer is rated at 18 MVA and 138/69 kV. Current transformers on the tertiary winding phases supply current to several directional relays and an overcurrent relay in the application described. Thus tertiary current fluctuations have the capability of causing transmission line service interruptions.
Keywords
Current transformers; Geomagnetism; Power system harmonics; Power system interconnection; Power system modeling; Power system relaying; Power system simulation; Power transmission lines; Relays; Silicon carbide;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1982.317277
Filename
4111372