• DocumentCode
    1165635
  • Title

    Fault in Ducte Voltages on Metallic Fencing Located in the Vicinity of a High Voltage Substation

  • Author

    Rogers, Eldon J. ; Hall, Ralph H. ; White, John F.

  • Author_Institution
    Bonneville Power Administration
  • Issue
    3
  • fYear
    1982
  • fDate
    3/1/1982 12:00:00 AM
  • Firstpage
    746
  • Lastpage
    750
  • Abstract
    Elements of public safety must be considered when metallic fencing is installed in the fault induced field of a substation. A formula is developed to estimate induced voltage on metallic fencing located adjacent to high voltage substations. A method is presented to estimate grid potential distribution. Verification is made using a fence model alongside a test grid. And, an example is given of a hazardous voltage which could be induced on metallic fencing during a line to ground fault.
  • Keywords
    Circuit faults; Concrete; Conductivity; Earth; Equations; Equivalent circuits; Safety; Substations; Testing; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1982.317290
  • Filename