• DocumentCode
    1165641
  • Title

    Particles and Moisture Effect on Dielectric Strength of Transformer Oil Using VDE Electrodes

  • Author

    Miners, Kamal

  • Author_Institution
    Allied Corporation
  • Issue
    3
  • fYear
    1982
  • fDate
    3/1/1982 12:00:00 AM
  • Firstpage
    751
  • Lastpage
    756
  • Abstract
    The effect of particles and moisture on the 60 Hertz breakdown strength of tranformer oil was investigated. Different sizes and concentrations of iron, copper and cellulose particles were used. The breakdown voltage was determined according to ASTM D1816 using VDE electrodes with an 80 mil (2 mm) gap. The breakdown strength of oil decreased approximately 25 percent when the moisture content was increased from 5 ppm to 20 ppm. A further reduction in the breakdown strength of oil occurred when iron, copper or cellulose particles were added to the oil. The transformer oil showed very low values of 60 Hertz breakdown strength as the result of the combined effects of moisture and particles´ type, size and concentration.
  • Keywords
    Dielectric breakdown; Electric breakdown; Electrodes; Iron; Moisture; Oil insulation; Petroleum; Power transformer insulation; Testing; Water pollution;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1982.317291
  • Filename
    4111386