DocumentCode
1166359
Title
Automatic Adjustment of Generator Voltages in Newton-Raphson Mehtod of Power Flow Solutions
Author
Mamandur, K.R.C. ; Berg, G.J.
Author_Institution
Ebasco Services, Inc. Two World Trade Centre
Issue
6
fYear
1982
fDate
6/1/1982 12:00:00 AM
Firstpage
1400
Lastpage
1409
Abstract
A method of considering the reactive power (var) limits of generators and their voltage adjustments, as a part of the Newton-Raphson power flow solution, is presented in this paper. The approach considers an extended Jacobian matrix of the standard Newton- Raphson method to include these variables in the problem formulation. Then, by suitable matrix manipulation techniques, the procedure estimates the generator voltage adjustments required to eliminate respective var limit violations. By the use of an efficient logic, the procedure limits the voltage adjustments to a minimum number of generators. The proposed technique complements other automatic adjustment features such as area interchange, transformer tap and phase-shifter controls that are already available with the Newton-Raphson technique.
Keywords
Automatic control; Equations; Jacobian matrices; Load flow; Logic; Power generation; Power systems; Reactive power; Samarium; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1982.317187
Filename
4111474
Link To Document