DocumentCode :
1166524
Title :
Three Phase Dynamic Simulation of Air Blast Generator Circuit Breakers -- Theory and Modeling
Author :
Prasad, N.R. ; Herling, S.R.
Author_Institution :
American Electric Power Service Corp.
Issue :
6
fYear :
1982
fDate :
6/1/1982 12:00:00 AM
Firstpage :
1561
Lastpage :
1569
Abstract :
Simulations of three-phase faults at the generator terminals have shown the existence of non-zero currents in all three phases for several cycles. Particularly in the application of generator circuit breakers, there could be a serious problem in that the delayed current-zero phenomenon might inhibit normal circuit opening. This investigation was undertaken to develop a method of modeling the circuit breaker arcing characteristics and determine the influence of arc gap resistance on the normal fault current decay. The paper presents the fundamental theory of the non-zero current phenomenon along with the basic operation and modeling of typical air-blast circuit breakers.
Keywords :
Circuit breakers; Circuit faults; Circuit simulation; Computer simulation; Delay; Fault currents; Power generation; Power system modeling; Samarium; Synchronous generators;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1982.317205
Filename :
4111492