DocumentCode
1166779
Title
T-T Tranformer Analysis and Application
Author
Smith, D.R. ; Neupauer, J.C. ; Braunstein, H.R.
Author_Institution
Westinghouse Electric Corporation
Issue
6
fYear
1982
fDate
6/1/1982 12:00:00 AM
Firstpage
1794
Lastpage
1804
Abstract
Equations are presented for calculating the self and mutual sequence impedances of T-T transformers with either a zero degree or 30 degree phase shift and either with or without a grounded neutral on the secondary teaser winding. It is shown that the voltage unbalance caused by the unsymmetrical characteristics of the T-T unit is less than 0.2 percent and 0.4 percent for units with 30 degree and zero degree phase shift respectively. Maximum values of secondary fault current can be determined by neglecting mutual sequence impedances and assuming the sequence self impedances are a fixed percentage of the nameplate impedance of the transformer.
Keywords
Assembly; Ferroresonance; Hydrogen; Impedance; Phase transformers; Power & Energy Society; Power cables; Printing; Surges; Transformer cores;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1982.317233
Filename
4111520
Link To Document