DocumentCode
1166861
Title
Comparison of simulated power system dynamics applying various load models with actual recorded data
Author
Kao, Wen-Shiow ; Lin, Chia-Jen ; Huang, Chiang-Tsang ; Chen, Yung-Tien ; Chiou, Chiew-Yann
Author_Institution
Dept. of Electr. Eng., Taipei Inst. of Technol., Taiwan
Volume
9
Issue
1
fYear
1994
fDate
2/1/1994 12:00:00 AM
Firstpage
248
Lastpage
254
Abstract
Time domain stability simulation results using derived load models were compared with corresponding data obtained from transient disturbance recorders to validate the accuracy of the load models. Observations of real and reactive power load responses at primary substations and real and reactive power flows on major trunk lines indicated that using a composite (dynamic and static) load model provides a more accurate representation than other models, and closely matches the actual recorded values from the Taipower System. A severe fault, during which enormous voltage and frequency excursions occurred in the system, was extensively examined considering load rejection due to large voltage drops
Keywords
load flow; power system analysis computing; power system stability; reactive power; time-domain analysis; Taipower System; composite load model; fault; frequency excursions; load models; load rejection; reactive power flows; reactive power load responses; real power load responses; simulated power system dynamics; substations; time domain stability simulation; transient disturbance recorders; trunk lines; voltage drops; voltage excursions; Frequency; Load modeling; Power system dynamics; Power system modeling; Power system simulation; Power system stability; Power system transients; Reactive power; Substations; Voltage;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.317604