DocumentCode :
1166990
Title :
Development of HVDC Circuit Breaker and its Interrupting Test
Author :
Yanabu, S. ; Tamagawa, T. ; Irokawa, S. ; Horiuchi, T. ; Tomimuro, S.
Author_Institution :
Toshiba Corporation
Issue :
7
fYear :
1982
fDate :
7/1/1982 12:00:00 AM
Firstpage :
1958
Lastpage :
1965
Abstract :
The authors have developed a DC circuit breaker (DCCB) which interrupts a DC current by injecting a high-frequency reverse current from a commutating capacitor to be superposed to DC current and forcibly creating a current zero point. A breaking part consists of a vacuum interrupters or a SF6 gas, interrupters of the most advanced design connected in series or in combination to attain a high interrupting capabilities. The commutating current is introduced into the interrupter through a pulse transformer so that DCCB can be conveniently used in the system. A 25OkV-3500A DCCB system with these features was designed, manufactured and tested with successful results.
Keywords :
Capacitors; Circuit breakers; Circuit testing; HVDC transmission; Interrupters; Magnetic switching; Power system reliability; Sulfur hexafluoride; Switches; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1982.317441
Filename :
4111545