Abstract
Tests to assess the reliability of a power line carrier system during sustained line faults have shown that a carrier operating range of about 60 db (decibels), in addition to that required for normal line attenuation, should permit reliable operation through faults. The use of line-to-line coupling provides no more than 8 db advantage over line-to-ground coupling.
Keywords
Attenuation measurement; Circuit faults; Circuit noise; Coupling circuits; Power system faults; Power system reliability; Power system transients; Protective relaying; Supervisory control; Testing;