DocumentCode :
1167669
Title :
Prevention of Covered Conductor Burndown on Distribution Circuits-Arcing Protection Devices
Author :
Lee, Robert E. ; Fritz, Donald E. ; Stiller, Paul H. ; Shankle, Derrill F.
Author_Institution :
Pennsylvania Power & Light Company
Issue :
8
fYear :
1982
Firstpage :
2434
Lastpage :
2438
Abstract :
The mechanism of covered conductor burndown is discussed in light of experience by the Pennsylvania Power and Light Company (PP&L) on 12-kV distribution circuits. A summary of laboratory test results is given to allow extension of this work to other distribution circuits. Details and early field experience are included on the Arcing Protection Device (APD), selected in an earlier study1 as the superior burndown prevention technique.
Keywords :
Circuit faults; Circuit testing; Conducting materials; Conductors; Fault currents; Insulation; Laboratories; Lightning; Protection; Surface impedance;