• DocumentCode
    1167675
  • Title

    Reset Characteristics of Automatic Resetting Type Fault Indicators on Three-Phase URD Systems

  • Author

    Thomas, Harry ; Kalmuck, John

  • Author_Institution
    Long Island Lighting Company
  • Issue
    8
  • fYear
    1982
  • Firstpage
    2439
  • Lastpage
    2442
  • Abstract
    The need for reliable fault indication in industrial parks has never been greater than it is today. For the most part, these areas are serviced by three-phase multi-legged core padmount transformers. If single-phasing occurs, a voltage induced in the open leg could cause automatic resetting type fault indicators to incorrectly reset as a result. This paper deals with such a situation and its solution. Studies and tests by Long Island Lighting and RTE determined the magnitude of the incident, its affect on associated equipment, and what new product application information resulted.
  • Keywords
    Automatic testing; Cables; Circuit faults; Circuit testing; Electrical equipment industry; Fuses; Leg; Personnel; Transformer cores; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1982.317604
  • Filename
    4111620