DocumentCode :
1168411
Title :
Pressure Drop and Heat Transfer in Entrance and Exit Chambers of Forced Cooled High Pressure Oil Filled Cable Systems
Author :
Willyard, J.H. ; Chato, J.C. ; Crowley, J.M.
Author_Institution :
Sundstrand Corporation
Issue :
9
fYear :
1982
Firstpage :
3028
Lastpage :
3035
Abstract :
Full-scale experiments were conducted on ten designs of terminator diffusion chambers for forced convectively cooled, high-pressure, oil-filled (HPOF), underground, pipe-type cable systems. Both hydrodynamic and thermal characteristics were determined in the entrance and exit flow mode. Pressure drop results were correlated in terms of the pressure loss coefficient as a function of the Reynolds number in the feed pipe. The heat transfer results were correlated in terms of the Nusselt number, based on cable diameter, as a function of both the same Reynolds number and the axial distance from the inlet.
Keywords :
Cable shielding; Cooling; Heat transfer; Hydrodynamics; Industrial engineering; Mechanical cables; Oil filled cables; Petroleum; Power cables; Temperature;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1982.317546