Ground Resistance-Revisited
Author
Jerrings, Donald I. ; Linders, John R.
Author_Institution
Nordon R & D, Inc., Clearwater, Florida
Volume
9
Issue
4
fYear
1989
fDate
4/1/1989 12:00:00 AM
Firstpage
54
Lastpage
54
Abstract
The nature of ground resistance is examined to explain the high impedance of faults directly to ground as contrasted to conventionally assumed low impedance ground faults to neutral conductor or to towers with low footing resistance. High impedance faults are shown to be inherently nonlinear due to the characteristics of soil. This nonlinearity is shown to be different from that of the arcing between conductor and ground. The harmonic content of the resulting current is judged to have characteristics which can be used to distinguish such faults from normal load variations.
Keywords
Conductors; Electric resistance; Fault currents; Grounding; Impedance; Power system harmonics; Protection; Soil; Surface resistance; Testing; ground faults; harmonics; high impedance;