DocumentCode :
1169297
Title :
Ground Fault by Restriking Surge of SF6 Gas-Insulated Disconnecting Switching and its Synthetic Tests
Author :
Nishiwaki, S. ; Kanno, Y. ; Sato, S. ; Haginomori, E. ; Yamashita, S. ; Yanabu, S.
Author_Institution :
Toshiba Corporation
Issue :
1
fYear :
1983
Firstpage :
219
Lastpage :
227
Abstract :
During a breaking operation of charging current with a disconnecting switch (DS) in SF6 gas-insulated switchgear (GIS), the occurrence of a fault to ground from the DS contact by a restriking surge was reported to be observed. The flashover voltage in this case, is appreciably lower than the normal withstand voltage to the ground. It has been clarified through high-speed photography with an image converter camera that the flashover is caused by a streamer generated during restriking between the DS contacts. In this respect, with the objective of confirming these phenomena in a simulated power system, two synthetic test circuits were constructed by using 550kV DS´s. Verification tests were carried out to confirm the equivalence between these two test circuits. The DS´s subjected to test withstood a surge voltage of 2.3pu-the maximum voltage obtained by simulating calculations of various GIS configurations.
Keywords :
Circuit faults; Circuit testing; Gas insulation; Geographic Information Systems; Power system simulation; Sulfur hexafluoride; Surges; Switches; Switchgear; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1983.318019
Filename :
4111811
Link To Document :
بازگشت