DocumentCode :
1169454
Title :
HVDC Models Used in Stability Studies
Author :
Johnson, Bradley K.
Author_Institution :
Power Technologies, Inc. 1482 Erie Boulevard P.O. Box 1058 Schenectady, NY
Volume :
9
Issue :
4
fYear :
1989
fDate :
4/1/1989 12:00:00 AM
Firstpage :
76
Lastpage :
77
Abstract :
Power system ac/dc stability simulation results obtained using three types of HVDC models are compared. The difference in results is shown to be much smaller than the level of uncertainty inherently involved in stability calculations. The theoretical basis for the two commonly used types of HVDC models is discussed and a third model is introduced which uses less computer time than the most detailed model and is more accurate than the simpler model. AC system harmonics and asymmetries cannot generally be represented in power system stability programs so the effects of harmonics and asymmetries on the HVDC system also cannot be modeled. Simulation results obtained using different assumptions regarding the HVDC converters response to ac system asymmetries, different assumptions regarding commutation failure and different ac system load models are compared to estimate the level of uncertainty inherent in the normal stability calculations.
Keywords :
Computational modeling; HVDC transmission; Inverters; Load modeling; Power system harmonics; Power system modeling; Power system simulation; Power system stability; Rectifiers; Uncertainty;
fLanguage :
English
Journal_Title :
Power Engineering Review, IEEE
Publisher :
ieee
ISSN :
0272-1724
Type :
jour
DOI :
10.1109/MPER.1989.4310615
Filename :
4310615
Link To Document :
بازگشت