    Transformer Tap Position Estimation

  • Author

    Fletcher, D.L. ; Stadlin, W.O.

  • Author_Institution
    Leeds & Northrup Company
  • Issue
    11
  • fYear
    1983
  • Firstpage
    3680
  • Lastpage
    3686
  • Abstract
    The estimation of voltage transformer tap position is a desirable feature that can be appended to most State Estimation algorithms. The primary requirement to estimate transformer tap position is the availability of a three phase reactive power measurement through either the fixed or tap side of the transformer. These "measured" flows can also be calculated, depending on the availability of reactive injection and reactive transmission line flow measurements around the fixed or tap side buses. The gain matrix of the State Estimator is not modified so only the tables used to calculate real and reactive residual mismatch need to be updated during the State Estimator solution. The computational cost of including transformer tap position estimationis extra iterations of the State Estimator.
  • Keywords
    Availability; Fluid flow measurement; Phase estimation; Position measurement; Power measurement; Reactive power; State estimation; Transmission line matrix methods; Transmission line measurements; Voltage transformers;