Title :
The AC Clean-Fog Test for Contaminated Insulators
fDate :
3/1/1983 12:00:00 AM
Abstract :
The paper* summarizes the results of clean-fog tests conducted by eleven task-force laboratories on a common suspension insulator, IEEE insulator.** The test series done according to a specific set of guidelines, show considerable dispersion in the fifty per cent flashover voltage between the laboratories. The significant parameters of the clean-fog method that influence the fifty per cent flashover voltage are discussed. More controls in testing are needed before the formalization of the clean-fog method as a standard contamination test for high voltage ac insulators can be made.
Keywords :
Contamination; Flashover; Insulation; Insulator testing; Laboratories; Lightning; Performance evaluation; Power & Energy Society; Sea measurements; Voltage;
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
DOI :
10.1109/TPAS.1983.317981