DocumentCode
1171208
Title
A New Measurement Technique for Tracking Voltage Phasors, Local System Frequency, and Rate of Change of Frequency
Author
Phadke, A.G. ; Thorp, J.S. ; Adamiak, M.G.
Author_Institution
VPI & SU
Issue
5
fYear
1983
fDate
5/1/1983 12:00:00 AM
Firstpage
1025
Lastpage
1038
Abstract
With the advent of Substation Computer Systems dedicated to protection, control and data logging functions in a Substation, it becomes possible to develop new applications which can utilize the processing power available within the substation. The microcomputer based Symmetrical Component Distance Relay (SCDR) described in the references cited at the end of this paper possesses certain characteristics which facilitate real-time monitoring of positive sequence voltage phasor at the local power system bus. With a regression analysis the frequency and rate-of-change of frequency at the bus can also be determined from the positive sequence voltage phase angle. This paper describes the theoretical basis of these computations and describes results of experiments performed in the AEP power system simulation laboratory. Plans for future field tests on the AEP system are also outlined.
Keywords
Application software; Control systems; Frequency; Measurement techniques; Microcomputers; Power system analysis computing; Power system protection; Power system simulation; Substation protection; Voltage;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1983.318043
Filename
4112036
Link To Document