• DocumentCode
    1171307
  • Title

    Evaluation of a Functional Life Test Model for Power Transformers

  • Author

    McNutt, W.J. ; Kaufmann, G.H.

  • Author_Institution
    General Electrical Company
  • Issue
    5
  • fYear
    1983
  • fDate
    5/1/1983 12:00:00 AM
  • Firstpage
    1151
  • Lastpage
    1162
  • Abstract
    A power transformer life model and its related, test procedure have been evaluated and found to provide more meaningful information on retained operational capability of the winding insulation than can be derived from simple material tests. Both paper and enamel conductor insulation demonstrated retained functional ity after aging for time periods in excess of 5 times the life defined in industry loading guides. In addition, valuable knowledge was revealed about the behavior of conductor turn insulation with free gas entrapment, where the gas source was either oil supersaturation with dissolved gas or thermal evolution from overheated cellulose.
  • Keywords
    Aging; Conducting materials; Gas insulation; Insulation testing; Life testing; Materials testing; Oil insulation; Petroleum; Power transformer insulation; Power transformers;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1983.318055
  • Filename
    4112048