DocumentCode
1171307
Title
Evaluation of a Functional Life Test Model for Power Transformers
Author
McNutt, W.J. ; Kaufmann, G.H.
Author_Institution
General Electrical Company
Issue
5
fYear
1983
fDate
5/1/1983 12:00:00 AM
Firstpage
1151
Lastpage
1162
Abstract
A power transformer life model and its related, test procedure have been evaluated and found to provide more meaningful information on retained operational capability of the winding insulation than can be derived from simple material tests. Both paper and enamel conductor insulation demonstrated retained functional ity after aging for time periods in excess of 5 times the life defined in industry loading guides. In addition, valuable knowledge was revealed about the behavior of conductor turn insulation with free gas entrapment, where the gas source was either oil supersaturation with dissolved gas or thermal evolution from overheated cellulose.
Keywords
Aging; Conducting materials; Gas insulation; Insulation testing; Life testing; Materials testing; Oil insulation; Petroleum; Power transformer insulation; Power transformers;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1983.318055
Filename
4112048
Link To Document