• DocumentCode
    1171670
  • Title

    Particle Contamination Levels in Oil-Filled Large Power Transformers

  • Author

    Oommen, T.V. ; Petrie, E.M.

  • Author_Institution
    Westinghouse Electric Corporation Large Power Transformer Division
  • Issue
    5
  • fYear
    1983
  • fDate
    5/1/1983 12:00:00 AM
  • Firstpage
    1459
  • Lastpage
    1465
  • Abstract
    A study of particle levels in transformer oil was conducted, covering about 200 samples taken from field and factory units. Factory samples were included to determine a relative base condition on which to compare field data. Particle distribution curves show size and count relationship in transformers. The particles were studied also by Atomic Absorption Spectroscopy to measure the content of iron, copper and other common metals expected. Particle analysis can supplement more standard laboratory techniques to judge the condition of oil in operating power transformers. The diagnostic value of such analysis, especially in determining pump performance problems, is illustrated with examples.
  • Keywords
    Absorption; Atomic measurements; Contamination; Iron; Oil insulation; Particle measurements; Pollution measurement; Power transformers; Production facilities; Spectroscopy;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1983.318066
  • Filename
    4112090