Title :
Switching-Surge and Dynamic Voltage Study of Arizona Public Service Company´s Proposed 345-Kv Transmission System Utilizing Miniature Analyzer Techniques
Author :
Croft, W.H. ; Hartley, R.H. ; Linden, R.L. ; Wilson, D.D.
fDate :
4/1/1962 12:00:00 AM
Abstract :
Investigations were conducted of switching-surge phenomena on the proposed addition of the 292-mile 345-kv transmission lines to Arizona Public Service Company´s system. In order to arrive at balanced design and operating conditions with regard to surge voltages, insulation levels, arrester protection, and switching procedures, a study was performed on a system in miniature. Data, results, and conclusions from this study are presented.
Keywords :
Arresters; Circuit testing; Insulation testing; Power system transients; Shape; Substations; Surge protection; Switching circuits; System testing; Voltage;
Journal_Title :
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
DOI :
10.1109/AIEEPAS.1962.4501321