• DocumentCode
    1172472
  • Title

    The Surge Performance of Cable-Connected Pad-Mounted Distribution Transformers

  • Author

    Armstrong, H.R. ; Charneski, M.D. ; Curto, R.T.

  • Volume
    81
  • Issue
    3
  • fYear
    1962
  • fDate
    4/1/1962 12:00:00 AM
  • Firstpage
    716
  • Lastpage
    719
  • Abstract
    The lightning protection of pad-mounted distribution transformers supplied through buried cable from open-wire circuits was investigated in the laboratory. Several distribution transformers and field lengths of equivalent cable were connected to form a typical underground distribution layout of limited size. Cost and space limitations in providing valve-type arresters at each transformer place emphasis on obtaining over-all protection from only the cable-open wire-junction arresters. The influence of wave shape, cable length and characteristics, and the relation of the transformer basic impulse insulation level (BIL) were considered.
  • Keywords
    Arresters; Circuits; Costs; Laboratories; Lightning protection; Power cable insulation; Power cables; Shape; Surge protection; Transformers;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
  • Publisher
    ieee
  • ISSN
    0097-2460
  • Type

    jour

  • DOI
    10.1109/AIEEPAS.1962.4501401
  • Filename
    4501401