DocumentCode :
1172717
Title :
Service Records of Cougnard Deionisers AIEE Committee Report
Volume :
81
Issue :
3
fYear :
1962
fDate :
4/1/1962 12:00:00 AM
Firstpage :
830
Lastpage :
832
Abstract :
Cougnard deionisers, elementally plane electrodes on the line insulator, are lightning protective devices of controversial theory. Data on lightning outage experince of 14 deioniser-equipped lines have beenl compared with their records before deioniser installation, or with records of similar conventional lines. On the basis of data obtained, and statemets of user opinion, the Working Group has concluded that the installation of Cougnard deionisers will neither improve nor degrade the lightning outage record of a line.
Keywords :
Cable shielding; Circuit faults; Coupling circuits; Equivalent circuits; Power cables; Power system analysis computing; Saturation magnetization; Surges; Switches; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
Publisher :
ieee
ISSN :
0097-2460
Type :
jour
DOI :
10.1109/AIEEPAS.1962.4501431
Filename :
4501431
Link To Document :
بازگشت