• DocumentCode
    1172839
  • Title

    Emissivity of Weathered Conductors After Service in Rural and Industrial Environments

  • Author

    Rigdon, W.S. ; House, H.E. ; Grosh, R.J. ; Cottingham, W.B.

  • Volume
    81
  • Issue
    3
  • fYear
    1962
  • fDate
    4/1/1962 12:00:00 AM
  • Firstpage
    891
  • Lastpage
    896
  • Abstract
    It has been recognized for many years that well-weathered conductors, after being energized for a period of time, have a dark surface resulting in an emissivity sometimes as high as 0.98, whereas a new conductor has an emissivity of approximately 0.23. The length of time needed to develop a high emissivity with the consequent higher current capability is of interest. Samples from various parts of the United States, with the time of service been collected and the emissivity determined. A conductor energized at 500 kv for 1 year at Leadville, Colo., at an altitude of 10,500 feet above sea level, had the same emissivity, 0.23, as a new conductor.