    Electrical Features of the Glen Canyon Power Plant and Switchyard

  • Author

    Rose, C.L. ; Lloyd, L.W.

  • Volume
    81
  • Issue
    3
  • fYear
    1962
  • fDate
    4/1/1962 12:00:00 AM
  • Firstpage
    901
  • Lastpage
    906
  • Abstract
    The Glen Canyon power plant has eight 125,000-kva 0.90-power-factor 13.8-kv generators. Power is transformed from generator voltage by three banks of 345-13.7-kv single-phase FOW (oil-immersed forced-oil-cooled with forced-water cooler) transformers and one bank of 230-13.8-kv single-phase FOW transformers. Switching facilities consisting of a 345-kv ring bus using six circuit breakers and a 7-breaker 230-kv installation are provided to connect the power plant circuits to the transmission system.
  • Keywords
    Bridge circuits; Circuit breakers; Power generation; Power transmission lines; Reservoirs; Rivers; Surges; Switching circuits; Transformers; Turbines;