Title : 
Voltage Induction in Parallel Transmission Circuits
         
        
        
        
        
        
            fDate : 
4/1/1962 12:00:00 AM
         
        
        
        
            Abstract : 
General formulas are developed with calculation examples for determining the positive-, negative-, and zero-sequence voltage induced in transmission circuits paralleled either on the same tower or on adjacent towers. For nontransposed lines the induced voltages are a function of all three sequence currents. The positive-and negative-sequence mutual impedance is less than 10% of the self-impedance of the lines while the zero-sequence mutual impedance can be as high as 50 to 70% of the zero-sequence self-impedance of the lines. The conductor configuration should be symmetrical around a vertical axis to avoid differences in the induced voltages in the two circuits.
         
        
            Keywords : 
Circuits; Costs; Fires; Grounding; Information resources; Measurement units; Polarization; Relays; Security; Voltage transformers;
         
        
        
            Journal_Title : 
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
         
        
        
        
        
            DOI : 
10.1109/AIEEPAS.1962.4501454