DocumentCode :
1173040
Title :
Single-Phase Autoreclosure on the 330-Kv Kariba Transmission System
Author :
Wilcox, T.W. ; Hore, R.A.
Volume :
81
Issue :
3
fYear :
1962
fDate :
4/1/1962 12:00:00 AM
Firstpage :
999
Lastpage :
1006
Abstract :
The paper reviews the application of autoreclosure to extra-high-voltage (EHV) transmission systems and examines the relative merits of 3-phase and singlephase autoreclosure. Laboratory experiments for determining the behavior of the residual are during single-phase autoreclosure are described, and results given of tests at a switchgear test plant simulating conditions for 270 miles of 330-kv line. Corroborative field tests and system operating experience are recorded indicating satisfactory performance of single-phase autoreclosure on 330-kv lines up to 200 miles long.
Keywords :
Circuit breakers; Circuit faults; Circuit stability; Delay; Hazards; Laboratories; Power generation; Switchgear; Testing; Voltage;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
Publisher :
ieee
ISSN :
0097-2460
Type :
jour
DOI :
10.1109/AIEEPAS.1962.4501473
Filename :
4501473
Link To Document :