• DocumentCode
    1173584
  • Title

    An Adaptive Scheme for Parallel Line Distance Protection

  • Author

    Hu, Ya ; Novosel, Damir ; Saha, Mousumi ; Leitloff, V.

  • Author_Institution
    ABB-USETI; ABB Automation Products AB; EDF R&D Division
  • Volume
    21
  • Issue
    10
  • fYear
    2001
  • Firstpage
    64
  • Lastpage
    64
  • Abstract
    This paper describes an adaptive protective relaying scheme for parallel-line distance protection. The scheme adjusts its operation, based on the availability of input signals, to achieve an optimal distance protection performance on parallel lines influenced by mutual coupling effect. When available, zero sequence current from the parallel line is used to fully compensate the mutual coupling effect. The zero sequence current ratio is used to avoid possible false operations on a healthy line, which may result from such compensation. When the parallel lines´ zero sequence current is not available, the line operating status is used instead to select proper zero sequence current compensation factors in impedance calculation. Default zero sequence current compensation factor is used when both parallel lines´ zero sequence current and line operating status signals are not available. The performance of the scheme has been verified on a simulated network and the results are presented.
  • Keywords
    Coils; Mutual coupling; Power system analysis computing; Power system harmonics; Power system reliability; Power transformers; Protective relaying; Short circuit currents; Surge protection; Voltage; Protective relaying; adaptive systems; coupled transmission lines; distance measurement; mutual coupling;
  • fLanguage
    English
  • Journal_Title
    Power Engineering Review, IEEE
  • Publisher
    ieee
  • ISSN
    0272-1724
  • Type

    jour

  • DOI
    10.1109/MPER.2001.4311109
  • Filename
    4311109